Borna portafusibles para 2 conductores; con portafusible basculante; y placa final; para fusible tipo G 5 x 20 mm; sin indicación de defecto; para carril DIN 35 x 15 y 35 x 7,5; 2,5 mm²; Push-in CAGE CLAMP®; 2,50 mm²; gris
Datos eléctricos
Note on max. power loss Pv max
When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
Power loss Pv max.
1.6 W
Note on power loss Pv
Overload and short circuit protection (Individual arrangement)
Power loss Pv max. 2
1.6 W
Note on power loss Pv 2
Overload and short circuit protection (Group arrangement)
Power loss Pv 3 max.
2.5 W
Note on power loss Pv 3
Short circuit protection only (Individual arrangement)
Power loss Pl 4 (max.)
2.5 W
Power loss Pl 4 (note)
Short circuit protection only (Group arrangement)
Ratings per IEC/EN
Datos asignados según
IEC/EN 60947-7-3
Tensión asignada (III / 3)
250 V
Tensión de choque asignada (III / 3)
6 kV
Corriente asignada
6.3 A
Leyenda datos asignados
(III / 3) ≙ Protección contra sobretensión III / Grado de ensuciamiento 3